AWM 3641 Fiberglass Braid Silicone Insulated Motor Wire
Conductor: Bare copper, tinned copper
Insulator: Silicone rubber
Jacket: Synthetic yarn braiding with silicone resin coating
Rated temp: 150/180℃
Rated volt: 3300V
Test Voltage: 7600V. 1min
Flame test: FT 2
Application
Thanks to the above characters, silicone wire & cable are used where high flexibility is required and high temperature conditions. AWM 3641 fiberglass braid silicone insulated motor wire is therefore a suitable connection cable for home electric appliance, high voltage machines like transformers, generators, motors, traction machines.
AWG NO. | Conductor | Insulation thickness | Braiding thickness | Cable OD | Resistance Ω/KM Max. | ||||
size | Structure | OD | Norminal | OD | Norminal | Tolerance | |||
mm² | No./mm | mm | mm | mm | mm | mm | mm | ||
16 | 1.31 | 7/0.49 | 1.55 | 1.8 | 5.15 | 0.2 | 5.60 | +0.30-0.20 | 14.6 |
26/0.254 | |||||||||
52/0.18 | |||||||||
15 | 1.65 | 33/0.254 | 1.75 | 1.80 | 5.35 | 0.20 | 5.80 | +0.30-0.20 | 11.3 |
14 | 2.08 | 41/0.254 | 1.95 | 1.8 | 5.55 | 0.2 | 6.00 | +0.30-0.20 | 8.96 |
7/0.62 | |||||||||
37/0.26 | |||||||||
13 | 2.63 | 52/0.254 | 2.15 | 1.80 | 5.75 | 0.20 | 6.20 | +0.30-0.20 | 7.10 |
12 | 3.31 | 65/0.254 | 2.5 | 1.80 | 6.1 | 0.2 | 6.50 | +0.30-0.20 | 5.64 |
43/0.32 | |||||||||
11 | 4.17 | 83/0.254 | 2.74 | 1.80 | 6.34 | 0.2 | 6.80 | +0.30-0.20 | 4.48 |
34/0.40 | |||||||||
10 | 5.261 | 35/0.45 | 3.20 | 1.80 | 6.80 | 0.20 | 7.20 | +0.30-0.20 | 3.55 |
9 | 6.631 | 53/0.40 | 3.98 | 1.80 | 7.58 | 0.25 | 8.10 | +0.30-0.20 | 2.81 |
8 | 8.367 | 70/0.40 | 4.40 | 1.80 | 8.00 | 0.25 | 8.50 | +0.30-0.20 | 2.30 |
7 | 10.55 | 84/0.40 | 4.60 | 1.80 | 8.20 | 0.25 | 8.70 | +0.30-0.20 | 1.79 |
6 | 13.30 | 105/0.40 | 5.30 | 1.80 | 8.90 | 0.30 | 9.50 | +0.30-0.20 | 1.42 |
5 | 16.77 | 133/0.40 | 6.00 | 1.80 | 9.60 | 0.30 | 10.2 | +0.40-0.20 | 1.12 |
4 | 21.15 | 168/0.40 | 6.80 | 1.80 | 10.40 | 0.30 | 11.0 | +0.40-0.20 | 0.89 |
3 | 26.67 | 210/0.40 | 7.60 | 1.80 | 11.20 | 0.30 | 11.8 | +0.40-0.20 | 0.707 |
2 | 33.62 | 266/0.40 | 8.50 | 1.80 | 12.10 | 0.55 | 13.2 | +0.40-0.20 | 0.56 |
1 | 42.41 | 217/0.50 | 9.60 | 1.80 | 13.20 | 0.55 | 14.3 | +0.40-0.20 | 0.449 |
1/0 | 53.49 | 276/0.50 | 11.2 | 1.80 | 14.80 | 0.55 | 15.9 | +0.40-0.20 | 0.355 |
2/0 | 67.43 | 342/0.50 | 12.2 | 1.80 | 15.80 | 0.55 | 16.9 | +0.40-0.20 | 0.282 |
3/0 | 85.01 | 437/0.50 | 13.8 | 1.80 | 17.40 | 0.65 | 18.7 | +0.40-0.20 | 0.223 |
4/0 | 107.2 | 551/0.50 | 15.5 | 1.80 | 19.10 | 0.65 | 20.4 | +1.0-0.50 | 0.177 |
250kcmil | 127.0 | 646/0.50 | 17.5 | 1.80 | 21.10 | 0.65 | 22.4 | +1.0-0.50 | 0.151 |
300kcmil | 152.0 | 779/0.50 | 19.5 | 1.80 | 23.10 | 0.65 | 24.4 | +1.0-0.50 | 0.125 |
350kcmil | 177.0 | 912/0.50 | 21.0 | 2.52 | 26.04 | 0.65 | 27.4 | +1.0-0.50 | 0.108 |
400kcmil | 203.0 | 1036/0.50 | 23.0 | 2.52 | 28.04 | 0.65 | 29.4 | +1.0-0.50 | 0.0942 |
300.0 | 1525/0.50 | 26.0 | 3.40 | 32.80 | 0.65 | 34.1 | +1.0-0.50 | 0.0654 |
Mechanical Properties
Tensile strength: ≥3.45N/mm²
Elongation at break of insulation: ≥100%
Min. bending radius: 6×OD
Standard: UL758, UL62, UL1581
Characteristics
AWM 3641 fiberglass braid silicone insulated motor wire has very good flexibility and good performance of resistance to high temperature, ranging from -55℃ up to 180℃.
The use of silicone rubber, a high grade corona resistant insulation material, gives the cable excellent dielectric strength.
The braided synthetic yarn covering, which is applied directly over the insulation, gives the cable, because of its short braiding pitch and high compactness, an excellent mechanical protection by maintaining good flexibility.
The varnishing of the braiding results in good antifriction properties, high abrasion resistance and excellent chemical resistance against transformer oil, light fuel oil and most types of cleaning agents.
In the event of fire, no corrosive and toxic gases will be given off.
Hence, damage caused by fire can be kept to minimum.