UserName: PassWord:
My account
My account
PL05 Pressure Switch (40-800 Pa),China PL05 Pressure Switch (40-800 Pa)
ETW International,ETW Manufacturers
P
PL05 Pressure Switch (40-800 Pa)

PL05 Pressure Switch (40-800 Pa)



The pressure switch employs a differential pressure to actuate a precision snap switch at chosen pressure setting. This may be the difference between atmospheric and a negative or positive pressure or between any two given pressures. When a change of pressure occurs between the negative pressure chamber and the positive pressure chamber the main diaphragm activates the snap switch at a predetermined value.
The pressure cut-off switch is manufactured from selected compound derivatives of polycarbonate & PBT offering exceptional thermal and dimensional stability at elevated temperatures up to 105 when used in contaminated atmospheres of air, products of combustion, L.P. or natural gas. It has been designed to meet the low pressure, high temperature specifications of future generations of fanned gas and similar appliances where differential pressures form part of an integral control systems.

Typical Applications
Detects air flow in forced draught appliances
Signals either positive, negative or zero air movement
Shut down burner in blocked flue conditions
Guards against poor or hazardous combustion
Indicates dirty or inefficient filters

Technical Data

Model

PL05

Medium

Air, products of combustion, L.P. or natural gas

Mounting /Fixing

4 screws with maximum penetration depth of 6.3mm into appropriate mounting holes, or fixed with optional bracket.

Mounting Position

The pressure switch is position sensitive. It may be mounted in most positions provided it has been calibrated.

Field Adjustable Range

0.4mbar to 8.0mbar make on positive or negative pressure rise. Minimum upper switching pressure 0.4mbar. Minimum lower switching pressure 0.2mbar.

Switch Differential

Not less than 0.1mb and not greater than 0.3mb depending on pressure settings.

Maximum Operating Pressure

10mbar =50Pa

Operating Temperature Range

105 Maximum

Electric Rating

125V, 250V, 5A single pole on-off or single pole change over. Other ratings are available on request.

Contact Arrangement

SPDT or SPST

Terminals

6.3 Or 4.88 mm male Q.C. Optional insulation cover available as necessary.

Calibration

PL05 switches are normally calibrated at their lower switching pressure in accordance with customer requirements.
Ramp rate at switch point=0.03mb/second

Calibration Tolerance

Standard production tolerance at ambient temperature is 0.10mb or 5% of set point, whichever is the greater.

Pressure Connections

6mm O.D. push on or "Permifix" tubing. The lower (negative) connector may be supplied in any one of four positions for ease of installation.

Note: 1mbar=100Pa 1"W.C.=1 in/H2O =249Pa

Feedback Form
Other Products
  • AFS Pressure Switches (12-2500 Pa) The AFS pressure switches are general purpose airflow proving switches designed for HVAC, detection of blocked filters and fan suction, air flow moni
  • HP-2 Pressure Switch The pressure switch is used for pressure controlling of Air, Water, Internal wiring of electric refrigerating equipment or room cooler units or remot
  • HP-3 Extended Duty Pressure Switch The extended duty pressure switch is specifically designed to stand up to extended duty applications. This switch is factory set but capable of field
  • HP-4 Vacuum Switch The vacuum switch is specifically designed to stand up to extended duty applications. This vacuum switch is factory set. It features a rubber diaphra
  • HP-5 High Pressure Switch The high pressure switches are robust, compact and designed to operate in harsh environments at various pressures. Because of its special internal de

United States | Argentina | Brazil | China | France | Germany | Japan | Korea | Russia | Spain | Switzerland | Thailand | UAE | United Kingdom | Vietnam | Poland | Italy | Morocco | Malaysia | Portugal | India | Canada

Copyright © 2008 - ETW International. All rights reserved.