- 13″ Rubber Pneumatic Wheel
- 10″ Hand Trolley Wheel
- 10″ Pneumatic Rubber Wheel
- Aluminum Hand Truck
- Light Platform Hand Truck
- Wheelbarrow Tire and Tube QAZ-5
- Wheelbarrow Tire and Tube QAZ-6
- Electric Skateboard Tire
- Wheelbarrow Tire and Tube QAZ-3
- Wheelbarrow Tire and Tube QAZ-4
- Wheelbarrow Tire and Tube QAZ-2
- Medium voltage VFD reconstruction case in thermal
- Application of Medium-voltage VFD in Thermal Power Plant
- Variable frequency reform of water feeding system in Yangpu Power Plant
- Medium voltage VFD application on 100MW mill fan
- Pneumatic Lawn Mower Tire
- 6″ Pneumatic Caster
- Concrete Mixer
- MV VFD application in Huayingshan Power Plant
- MV VFD application in 300MW turbine generator
- Snowblower Tire
- Lawn Mower Rubber Tire
- 6″ Solid Wheel
- Bicycle Tire
- The VFD application in Dalian Developing Zone Thermal Power Plant
- 16″ Flat Free Wheelbarrow Wheel
- Application of VFD on condensing pump in 300MW generator units
- 90° Scroll Saw
- 10″ Hand Cart PU Foam Wheel
- Motorcycle Tire
- Application of HARSVERT-A model Medium Voltage VFD in 600MW ultra-supercritical condenser ...
- Medium voltage VFD application in Liaocheng Thermal Power Plant
- Variable Frequency Control Technology on ID Fan in 300MW Generator Unit
- Spain Wheelbarrow
- Drum Dolly
- Construction Wheelbarrow
- South Africa Wheelbarrow
- France Wheelbarrow
- Engineering Wheelbarrow
- Garden Wheelbarrow
- Wheelbarrow Tire and Tube QAZ-1
- 10″ Crumb Rubber Wheel
- Double Wheel Wheelbarrow
- 8″ Flat Free Pneumatic Caster
- 10″ Flat Free Hand Truck Wheel
- 10″ Hand Truck Flat Free Wheel
- 8″ Solid Flat Free Wheel
- Yard Cart
- Construction One-wheel Wheelbarrow
- European Wheelbarrow
- 16″ Wheelbarrow Wheel
- 16″Wheelbarrow Wheel
- 16″ Wagon Pneumatic Wheel
- 16″ Rubber Wheel
- Anti-Fatigue Mat
- Rubber Tile Mat
- Application of Medium-voltage VFD in Dusting Fans for the Electric Furnaces of the Forth S...
- Vertical Drill Press
- Application of Harsvert VFD in Zibo Cement Plant
- Vector control VFD application in high-temperature fan
- Ladder
- Heavy Platform Hand Truck
- CVT Drill Press
- Hand Cart Tire
- 10″ Hand Truck Wheel
- Farm Wheelbarrow
- Agricultural Wheelbarrow
- One-wheel Wheelbarrow
- 8″ Pneumatic Caster
- High voltage VFD application in technics of desulfuration circulating pump
- 7 Cu.Ft Wheelbarrow
- Sack Truck
- Farm Cart
- Garden One-wheel Wheelbarrow
- Plastic Tray Wheelbarrow
- 5 Cu.Ft Wheelbarrow
- Heavy Load Wheelbarrow
- Medium voltage VFD application in Cangnan Water Plant and its energy saving analysis
- Heavy Duty Wheelbarrow
- Application of Medium-voltage VFD on Oil Pump Sets in Oilfields
- Application and Practice of Medium-voltage VFD in Water Injection System of Oilfield
- Hose Reel Cart
- Mexico Heavy Duty Wheelbarrow
- New way of power saving and emission reduction in oil refinery
High voltage VFD application in technics of desulfuration circulating pump
2009-12-21 11:33:24
Abstract: combining with practice state of Chuanxibei Natural Gas Purification Plant, this paper introduces Leader&Harvest VFD application in technics of desulfuration circulating pump.
Key words: high voltage VFD cell-cascade multi-level circulating pump constant pressure water supply energy saving
I.Preface
Chuanxibei Gas Purification Plant of West-south Oil&Gas Branch Company in PetroChina locates in Jiangyou city Sichuan province. It takes natural gas from Jiangyou Zhongba gas field as raw material and makes purification. It is a key enterprise in Sichuan with daily purifying capacity 500000m3. Its main products includes sulfur, liquified petroleum and natural gas. The products have been sold to domestic and foreign markets. This purification plant belongs to typical petroleum chemical industry. There are kinds of equipments with high value in plant, so it requires highly about security and continuous operation.
There are two pumps 1# and 2# in purification plant. One works and the other is spare. Two motors started in direct on line. Big start current affects equipment lifetime as well as power grid. In desulfuration technics, temperature difference between daylight and night is big. Circulating flow should be adjusted correspondingly. In original constant speed operation, flow was adjusted by valve opening. By changing pipe resistance and increasing throttle loss adjusted flow. Much energy wasting resulted in high power cost. Valve adjustment not only brought inferior economic benefit but also increased worker labour. If worker did not adjust in time, it would cause too high or too low pressure, too big or too small flow. In order to reduce dusulfuration cost and heighten technics precision and efficiency, it was urgent to innovate with technology of variable frequency for 1# and 2# pump.
After long term of research, inspection and comparison, the plant decided to use HARSVERT-A series VFD.
II. Project introduction
1.There are five parts in desulfuration system: cooling tower, middle tank, circulating pump, flooding pump and desulfuration device. Circulating hot water from desulfuration device flows to middle tank through cooling tower. Most water would reuse via desulfuration. Excessive water spills from flooding pipe. Please look at process drawing in following:
2. Technics requirement
a. Temperature difference of input/output cooling tower is constant
Temperature difference is required to be constant(4℃<△t<8℃). If valve opening of circulating pump increases, flow increases, temperature difference of cooling water reduces. If flow reduces, temperature difference increases.
b. Minimum pressure control
Ensuring inlet pressure of desulfuration device (more than 0.45Mpa), VFD should save circulating flow as much as possible and find the lowest critical pressure.
3. Site state
VFD room is 7200mm in length and 3000 in width. (the space is too small to install 2 VFDs in parallel)
4. Instruments and meter
A pressure transmitter: single route output current 4~20mA, load capacity300Ω (two wire).
A temperature difference transmitter: single route output current 4~20mA, load capacity300Ω (four wire).
5. Parameters of motor and pump
1#, 2# motor | 1#, 2# circulating pump | ||
Motor model | Y3556-4/YKK400-4 | Pump model | 14SH-9A |
Rated power | 315kW | Rated power | 315kW |
Rated voltage | 6kV | Rated flow | 1170m3/h |
Rated current | 37.7A | Rated lift | 65m |
Rated speed | 1475rpm | Rated speed | 1450rpm |
Power factor | 0.86 |
|
|
III. Commissioning and Scheme
1. Space
Take account of limited space, we decide to put VFD and bypass cabinet separatedly. 1#, 2# VFDs (3300×2574×1200 mm)install in parallel in VFD room and bypass cabinets install in pump site, which not only brings advantage to observe power delivering state but also solves problem of limited space.
2. Critical point
According to technics requirement, we get that pressure is sufficient condition of ensuring desulfuration production. Namely only when pressure reaches 0.46Mpa, the production can be ensured. If pressure of pump outlet is too low, it can not overcome potential energy of water and can not deliver circulating water to cooling tower. If the pressure is too high, output water of pump increases and efficient of cooling circulating water is low. So we decide to adopt control method of constant pressure close loop. Adjust given frequency of VFD and find the lowest critical point of pressure. This method can satisfy pressure demand and circulating flow demand, keep temperature difference of cooling tower in 4℃~8℃ stably. After repeated tests and demonstration, we get that when given frequency is 43Hz, pressure (0.51 Mpa) satisfies technics requirement, temperature difference is 4.92℃. So 43Hz is critical point.
Commissioning data:
Given frequency | Input voltage | Input current | Output voltage | Output current | Motor speed | Pressure feedback |
20Hz | 6.02 kV | 4.68A | 2.24 V | 8.64 A | 592rpm | 0.15 MPa |
30 Hz | 5.98 kV | 9.6A | 3.48 V | 10.8 A | 888 rpm | 0.25 MPa |
40 Hz | 5.98 kV | 14.4A | 4.74 V | 19.4 A | 1184 rpm | 0.45 MPa |
45 Hz | 5.98 kV | 22.6A | 5.40 V | 25.92 A | 1332 rpm | 0.55 MPa |
50 Hz | 5.94 kV | 27.8A | 5.82 V | 31.2 A | 1480 rpm | 0.72 MPa |
43 Hz | 5.98 kV | 19.3 A | 4.84 V | 23.74 A | 1272.8 rpm | 0.51 MPa |
42.5 Hz | 5.98 kV | 17.5 A | 4.76 V | 22.32 A | 1258 rpm | 0.48 MPa |
42 Hz | 5.94 kV | 17.1 A | 4.72 V | 22.2 A | 1243.2 rpm | 0.46 MPa |
3. Load capacity of transmitter
Because there is only one single route pressure transmitter of 300Ω in site, but input resistance of EM235 is 250Ω which is analogue input module of S7-200 PLC inside VFD. If analogue input circuits of 2 VFDs connect in series, input resistance of 2 EM235 is 500Ω. Single transmitter can not drive 2 pieces of EM235. So this method is infeasible. Therefore, we connect pressure transmitter to EM235 of single VFD, take advantage of module EM232 to output one route pressure of site. Make this output signal as analogue input of EM235 in the other VFD. Principal drawing is following:
In this method, no cost (hardware) added, by changing PLC programme makes EM232 of 1# VFD input a route pressure feedback signal instantly. It solves problem of insufficient capacity of pressure transmitter and realizes single pressure transmitter to drive 2 VFDs in close loop control.
IV. Energy saving calculation
Parameters of motor and pump:
Before VFD reform | After VFD reform(43Hz) | ||
Motor input voltage | 6000V | Motor input voltage | 4880V |
Motor input current | 28A | Motor input current | 23.76A |
Power factor | 0.86 | Power factor | 0.96 |
Valve opening | 75%~90% | Valve opening | 100% |
Flow | About 950 m3 /h | Flow | - |
Water pressure | 0.6MPa | Water pressure | 0.5 MPa |
In valve control mode, power consumption is product of flow Q and pressure H.
P70%=315×0.75×(1.4-0.4×0.75×0.75)=277.6KW
In VFD control mode, power consumption is:
PVFD=1.732×4880×23.76×0.96=192.8 kW
Energy saving rate is:(277.6-192.8)/277.6=30.5%
Yearly work time is 8000h, power price is 0.7yuan/kWh, cost saved of single pump is:
(277.6-192.8)×8000×0.70=475000yuan(USD 69750 )
V. Benefit of water saving
Because of special requirement of desulfuration technics, temperature difference of cooling tower decides circulating flow. Before VFD reform, in winter of big temperature difference, circulating flow demand was less. Excessive water was discharged from flooding pump, which caused much water wasted. After VFD reform, adjusting given frequency reduces circulating flow and ensures water temperature of desulfuration technics. Pump works in high efficient range and flooding loss is controlled.
VI. Concluding remarks
Practise proves that: HARSVERT-A06/040 VFD application in circulating pump of Chuanxibei Gas field is successful. Energy saving effect of VFD is obvious. Valve inlet/outlet opens fully, which reduces throttle loss. Soft start of motor prolongs motor lifetime. Inside PLC collects pressure data (4~20mA signal)from site, adjusts VFD output frequency automatically according to change of set value and actual value, implementing constant pressure water supply. VFD heightens automatization level of desulfuration technics and it has excellent utilization value.

- 8″ Pneumatic Caster 8″ Pneumatic Caster The 8″ pneumatic caster has 50mm symmetrical hub length and 16mm bore size. This

- One-wheel Wheelbarrow One-Wheel Wheelbarrow The one-wheel wheelbarrow has galvanized steel tray with thickness from 0.60mm to 1mm,

- Agricultural Wheelbarrow Agricultural Wheelbarrow The agricultural wheelbarrow has galvanized steel tray with thickness from 0.70 to 1

- Farm Wheelbarrow Farm Wheelbarrow The farm wheelbarrow has a tray made of galvanized steel with thickness between 0.70mm and 1.20mm

- 10″ Hand Truck Wheel 10″ Hand Truck Wheel The 10″ hand truck wheel is perfect for low-speed uses, including wagons, carts, hand tr


United Kingdom


English
Français
Español
Русский
العرب
Deutsch
Português
Tiếng Việt
Bahasa Malaysia
Polski
ภาษาไทย