ELE 12-24kV SF6 Ring Main Unit

ELE 12-24kV SF6 Ring Main Unit



ELE 12-24kV SF6 RingMain Unit

Productfeature

Fully Insulated and Sealed Design
ELEseries switchgear contains a stainless steel tank filledwith SF6 gas, in which the primary live parts, the busbar and switch contacts are kept. The bushing interfacedesign is via standardized outer cone bushings to EN 50180/50181 (DIN 47636),which connect the cables via insulated and shielded separable connectors. The ingress protection rating of the gas tank canreach IP67. Outside part of gas tank can resistshort-time flood and dewdrop because of special design and surface process.

Standard Modularize Design
Basicunits include loadbreak switchunit (module C andN), loadbreak switch-fusecombination unit(module T), circuitbreaker unit (moduleV and V0), busbar switchunit (module S, D, VS, VD),metering unit(module M), busbar PT unit(module P), cablefeeder unit (moduleB), Z unit, ZDunit etc…Different modules can be combined andassembled in one SF6 insulated tank.

Flexible Extensible Design
ELE-Fseries are un-extensible switchgear, combined by basic units in one tank. ELE-Eseries flexible extensible units provide the user with diversified solutions,for which different tank was connected electrically on the top by busbar connector.

Unique and Economic Solution for Power Cable Connection
ELEseries switch configuration scheme have outlet bushings on both sides. Itprovides unique and economic solution for multi-cable branching andsectionalizing system.

Service Conditions
1. Altitude: Notmore than 4000m.(If altitude exceed 1000m, please point out, so that pressure can beadjusted when manufacture.)
2. Ambienttemperature: +50℃ for maximum, -40℃ for minimum, no more than 35℃ for average ambient temperature within 24hrs.
3. Ambienthumidity: no more than 95% for average relative humidity within 24hrs, no more than 90% for averagerelative humidity within one moneh.
4.Installation condition: No explosive or corrosive gas in the ambient air; noshock and vibration at the field; pollution grade is not more than III gradedefined in standard GB/T 5582.
5. Accelerationof the earthquake: less than 0.3gin the horizontal direction, lessthan 0.15g in the verticaldirection.

Standards
GB3804-2004, 3.6Kv-40.5 kVHigh-voltage switches(IEC 60265-1:1998,MOD)
GB1984-2003 High-voltage circuit breaker
GB16926-1997, High-voltagealternating current switch-fuse combinations (equivalent to IEC 60420:1990)
GB1985-2004, High-voltagealternating current disconnectors and earthingswitches(IEC 62271-102:2002,MOD)
GB3906-2006, 3.6Kv-40.5 kV High-voltageswitchgear and control gear(IEC62271-200:2003,MOD)
Q/GDW-10-324-2008Technical specifications for 20KV medium voltage ring main switchgears
GB/T11022-1999, Commonspecifications for high-voltage switchgear and control gearstandards (equivalent to IEC 60694:1996)
GB/T11023-1989, Test guide of SF6gas tightness for high-voltage switchgear
GB4208-1993, Degrees ofprotection provided by enclosures (IP code) (equivalent to IEC 60529:1989)
GB/T5582-1993, External insulation pollution classes of high-voltage electric powerequipments (IEC 507:1991 REF)
DL/T404-1997 Technical specifications for ordering indoor A.C. metal-enclosedswitchgear (equivalent to IEC 60298:1981)
GB/T14436 General principles of industrial product guarantee documents
JB/T8754-1998Organization of the types of high-voltage switchgear and control gear
GB/T6388 Transport package shipping mark
GB/T13384, General specifications for packaging of mechanical and electrical products

Application
Because SF6-insulated ring main unit ismaintenance-free, compact and independent of altitude, dewdrop, contaminant,small animals and chemical substance etc., it is widely used at manypower-supplied systems, which has high level of reliability such as commercialcenter, industrial zone, airports and speedways. SF6-insulated ringmain unit can not only be used indoors or outdoor separately, but alsointegrated with high voltage/low-voltage prefabricatedsubstation. ELE series SF6-insulated ring mainunit wholly brought in advanced facilities and manufacture technology, and allour products are localized made in China. The competitive costs andprompt lead-time won good reputation in the market worldwide.

Technicalspecification

Item

Unit

C Unit

F Unit

V Unit

Rated voltage

kV

12/24

12/24

12/24

Rated frequency

Hz

50

50

50

Rated current

A

630

Depending on the current rating of the fuse.

630

Rated insulated level

1min. power frequency withstand voltage

(To earth & between phase)

1min. power frequency withstand voltage(Across the isolating distance)

1min. power frequency withstand voltage(Auxiliary and control circuits)

Rated lightning impulse withstand voltage(To earth & between phases)

Rated lightning impulse withstand voltage(Across the isolating distance)

kV

42/65

48/79

2/2

75/125

85/145

42/65

48/79

2/2

75/125

85/145

42/65

48/79

2/2

75/125

85/145

Rated Short-time withstand current(r.m.s)

kA

25/3s/20/3s

-

25/2S/20/4s

Rated peak withstand current

kA

63/50

-

63

Rated short-circuit making current(peak)

kA

63/50

Restricted by fuse

50

Rated short-circuit breaking current

kA

-

Restricted by fuse

20/20

Rated transfer current

A

-

17500/1400

-

Rated load-break current

A

630

-

-

Rated closed-loop breaking current

A

630

-

630

Mechanical operation

Loadbreak switch/circuit breaker

Disconnector/Earthing switch

time

5000

2000

5000

2000

10000

2000

Resistance of the main circuit

μΩ

≤120

-

≤120

Pressure of compressed gas

Rated pressure of compressed gas(absolute pressure)

Min. pressure of compressed gas(absolute pressure)

bar

1.3

1.2

1.3

1.2

1.3

1.2

Annual relative leakage rate of SF6gas

%

≤0.05

≤0.05

≤0.05


As a China ring main unit manufacturer, CEE provides a comprehensive range ofmedium voltage power distribution equipment, including bushing surge arrester,separable connector, overhead short circuit fault indicator, to name a few. Ourcompany has received the ISO9001 and ISO14001 certificates, and our productshave been CCC certified. We are located in Fuzhou City, Fujian Province, which providesus with easy access to convenient sea, land and air transportation.

Feedback Form
Other Products
  • 630A, 24kV Two Side Bushing 630A, 24kV Two Side BushingThe CEE CQTG-24/630 two side bushing is designed for power cable sector and switchgear. It provides two DIN47636 standard
  • 600A,35kV Integral Deadbreak Bushing 600A,35kV Integral DeadbreakBushingThe CEE YTGZD-35/600 integral deadbreak bushing combines the advantagesof reliable integral design with the operat
  • Metal Stamping Parts Metal Stamping Parts The metal stamping parts are usually made of cold rolled steel sheet or hot rolled steel sheet. They a

United States | Argentina | Brazil | China | France | Germany | Japan | Korea | Russia | Spain | Switzerland | Thailand | UAE | United Kingdom | Vietnam | Poland | Italy | Morocco | Malaysia | Portugal | India | Canada

Copyright © 2008 - ETW International. All rights reserved.