Standards The fire-resistant characteristics of the computer cable comply with GB /T 19216.21 (IEC60331-21) standards.
The flame-retardant cables comply with GB /T 18380 (IEC60332-3) standards.
The low- smoke and halogen-free cables comply with GB/T 17651(IEC61034), GB/T 17650.1 (IEC60754-1) standards.
The low- smoke and halogen-free cables comply with GB/T 17651(IEC61034), GB/T 17650.2 (IEC60754-2) standards.
U0/U: 300/500V

Application Our DCS system fire resistant instrumentation cable is used for high quality signal transmission and control in DCS systems applied to various industrial operations.

Specifications

No. Items Parameter
1. Rated voltage U0/U 300/500V
2. Max. Permissible continuous operating temperature of cable
PE insulated cable 70 ℃
XLPE insulated cable 90 ℃
PVC insulated cable 70 ℃ , 90 ℃
( LSHF PO) insulation cable Fluoroplastic insulation cable 90 ℃ 200 ℃
3. Min. laying temperature
PE sheathed cable -20 ℃
PVC or LSHF PO sheathed cable Fluoroplastic sheathed cable 0 ℃ -25 ℃
4. Permitted bending radius
Armored or wrapped shield ≥12D*
Other cables ≥6D*
Note: D is diameter of the cable